Online UPS · Outdoor cabinet · IP55
Outdoor UPS 1–10 kVA
A UPS, a battery bank and its climate control in one weatherproof cabinet. For sites where there is no plant room to put them in: telecom towers, roadside cabinets, water pumping stations and anywhere the equipment has to stand outside.
Five models: OTD110-1KVA / 2KVA / 3KVA / 6KVA / 10KVA. Battery capacity is chosen at order — 38, 65, 80 or 100 Ah.
Design highlights
Built for outside, not adapted for it
The enclosure is galvanised sheet with an outdoor powder coating, a sun shield, roof ventilation and a rain lip over the door. It is designed as an outdoor cabinet from the start, not a standard UPS put inside one.
Batteries are the part that fails first in heat and cold. Optional air-conditioning or a heat exchanger handles the upper end; an adjustable heater with thermostat handles the lower end.
115–295 Vac on the 1–3 kVA models, so a site with a poor supply stays on mains instead of cycling the battery every hour — which is what kills battery banks at remote sites.
Designed to run from a diesel set where the grid does not reach, with a soft start ramp of 0–100% in five seconds.
UPS, charger, battery and climate control share one cabinet, so the installation is one concrete pad and one cable run rather than three.
Technical specifications
OTD110 Series outdoor UPS
Five models, single phase, IP55 cabinet.
| Parameter | OTD110-1KVA | OTD110-2KVA | OTD110-3KVA | OTD110-6KVA | OTD110-10KVA |
|---|---|---|---|---|---|
| Capacity | |||||
| Capacity (kVA / kW) | 1 kVA / 0.9 kW | 2 kVA / 1.8 kW | 3 kVA / 2.7 kW | 6 kVA / 5.4 kW | 10 kVA / 9 kW |
| Nominal voltage | 220 / 230 / 240 Vac | ||||
| Frequency | 50 Hz / 60 Hz | ||||
| Input | |||||
| Voltage range | 115–295 Vac (±3) | 115–295 Vac (±3) | 115–295 Vac (±3) | 176–297 Vac (±3) | 176–297 Vac (±3) |
| Frequency range | 50 Hz (46–54 Hz); 60 Hz (56–64 Hz) | ||||
| Soft start | 0–100% in 5 s | ||||
| Input power factor | 0.98 | ||||
| Output | |||||
| Voltage precision | 220 / 230 / 240 Vac ±2% | ||||
| Frequency precision | 50 / 60 Hz ±0.05 Hz | ||||
| Output power factor | 0.9 | ||||
| Wave distortion | <3% linear load; <6% non-linear load | ||||
| Overload capability | 110–150% for 30 s, then transfers to bypass and returns automatically | ||||
| Crest factor | 3:1 | ||||
| Transfer time | 0 ms, AC to DC | ||||
| Battery | |||||
| DC supply voltage | 36 Vdc | 72 Vdc | 96 Vdc | 192 Vdc | 240 Vdc |
| Charging current | 4 A / 8 A optional | 4 A / 8 A optional | 4 A / 8 A optional | 4.2 A | 4.2 A |
| Internal battery capacity | 38 / 65 / 80 / 100 Ah, selected at order | ||||
| Interface | |||||
| LCD | Load level, battery level, battery indicator, utility, inverter, bypass, overload, fault | ||||
| Communication | RS232 standard; SNMP card optional | ||||
| Environment | |||||
| Operating temperature | −40 to 55 °C | ||||
| Storage temperature | −25 to 55 °C | ||||
| Humidity | 0–95% non-condensing | ||||
| Altitude | <1500 m | ||||
| Protection grade | IP55 / IP56 cabinet | ||||
| Physical | |||||
| Net weight, no battery | 85 kg | 125 kg | 125 kg | 150 kg | 150 kg |
| Dimensions W × D × H | 613×640×954 mm | 650×753×1227 mm | 650×753×1227 mm | 940×940×1770 mm | 940×940×1770 mm |
Specifications subject to change without notice. Air-conditioning, heat exchanger and heater are ordered as options and occupy part of the cabinet — confirm the configuration with the battery capacity together. Weights shown exclude batteries.
12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.
Installing where there is no plant room?
Tell us the site conditions — ambient temperature range, whether the grid is present, and the runtime required. We will size the cabinet, the battery and the climate option together.