SHINPOWIN™ Power Protection Request a quote
SHINPOWIN PT series 1-3 kVA online UPS with isolation transformer, front view with LCD

Online UPS · Galvanic isolation · 1–3 kVA

PT Series 1–3 kVA ISO

An online UPS with an isolation transformer on the output, built for the loads where neutral-to-earth voltage matters: laboratory instruments, imaging equipment and control systems that misbehave on a shared neutral.

1–3 kVACapacity
0 VNeutral to earth
90–285 VacInput window
0 msTransfer

Four models: 1K-ISO, 2K-ISO, 2K-ISO-plus and 3K-ISO. Internal battery with external module (EBM) option.

Design highlights

What galvanic isolation actually fixes

Zero volts neutral to earth

The transformer creates a real neutral reference instead of inheriting whatever the building's earthing happens to be — the usual cause of noise on measurement equipment.

Common-mode noise rejected

Isolation blocks the common-mode interference that travels along the neutral from other loads on the same distribution board.

Same protection as an online UPS

True double conversion, 0 ms transfer to battery, 90–285 Vac input window and >0.99 input power factor. The isolation is added, not traded against protection.

Small enough for a bench

17 to 36 kg in a tower chassis, with an external battery module connector for longer runtime.

Technical specifications

PT Series 1–3 kVA ISO

Four models, tower chassis, output isolation.

Parameter1K-ISO2K-ISO2K-ISO-plus3K-ISO
Capacity
Capacity (VA / W)1 kVA / 900 W2 kVA / 1.8 kW2 kVA / 1.8 kW3 kVA / 2.7 kW
TopologyDouble conversion online with galvanic isolation
AC mains input
Wiring1 phase 3 wires (L / N + PE)
Rated voltage208 / 220 / 230 / 240 Vac
Rated frequency50 / 60 Hz
Voltage range90–285 Vac ±5
Frequency range(40–70) ±0.5 Hz
Input power factor>0.99
Bypass voltage range180–265 Vac
Battery & charger
Rated battery voltage24 Vdc48 Vdc72 Vdc72 Vdc
Battery locationInternalInternal / EBMInternal / EBMInternal / EBM
Battery capacity12 V / 7 Ah × 2 pcs12 V / 7 Ah × 4 pcs12 V / 7 Ah × 6 pcs12 V / 7 Ah × 6 pcs
Backup time at half load>8 min
Charging current1 A on standard models with internal battery; 5.5 A on long-backup models
External batteryExternal battery module (EBM) connector available
AC output
Wiring1 phase 3 wires (L / N + PE)
Output voltage208 / 220 / 230 / 240 Vac
Output frequency50/60 Hz ±4 Hz sync mode; 50/60 Hz ±0.1% free run
Voltage regulation±1%
WaveformPure sine wave
Distortion (THDv)<2% linear load; <5% non-linear load
Output power factor0.9
Overload60 s at 105–125%; 60 s at 125–150%; 0.5 s above 150%
Transfer timeLine to battery 0 ms; inverter to bypass 4 ms
Interface
DisplayLCD — input voltage, frequency, load level, operating mode, health status
Standard interfacesRS232, USB (emulated serial, non-HID), EPO port, intelligent slot
Communication cardsNetwork card (SNMP/TCP-IP, app and web monitoring, server / NAS shutdown); CMC MODBUS card; AS400 relay card
Environment & physical
Operating temperature−10 to 50 °C
ChassisTower
Dimensions W × H × L400×180×260 mm425×190×328 mm425×190×328 mm425×190×328 mm
Weight17 kg32 kg36 kg36 kg

Specifications subject to change without notice. The 2K-ISO-plus adds the external battery module option to the standard 2K-ISO configuration. Isolation is continuous in line, battery and bypass modes.

Warranty

12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.

Protecting instruments that need a clean neutral?

Tell us the equipment and the symptom — noise, drifting readings, unexplained resets. We will tell you whether isolation is the fix or whether the problem is upstream.

Request a quote

Related products

Other platforms

GT Series · 6–20 kVA DP

GT Series · 6–20 kVA DP

Split-phase tower UPS with isolation and PF 1.0.

View series →
TD Series · 3–40 kVA

TD Series · 3–40 kVA

Low-frequency UPS with output isolation transformer.

View series →
SR Series · 1–20 kVA

SR Series · 1–20 kVA

Rack-mounted double-conversion UPS.

View series →