Online UPS · 208/220/230/240 Vac · PF 1.0

GT Series 1–10 kVA

The tower workhorse of the range: true double conversion from 1 to 10 kVA at 208/220/230/240 V, with output power factor 1.0 — a 10 kVA unit carries 10 kW, not 9.

1–10 kVACapacity
PF 1.0Output power factor
90–285 VacInput window
TowerChassis

Ten models: GT1K / GT2K / GT3K with internal battery, GT1KL / GT2KL / GT3KL for external banks, and GT6K / GT6KL / GT10K / GT10KL above 6 kVA.

Design highlights

Why output power factor 1.0 matters here

A 10 kVA unit really delivers 10 kW

Most UPS in this class are rated at 0.9 PF, so a 10 kVA unit carries 9 kW. At 1.0 the same frame carries 10 kW — often the difference between one model and the next size up, which is a real cost difference on a project.

90–285 Vac input on 1–3 kVA

Wide enough to ride out the brownouts and generator dips that a 208/220 V site actually sees. The UPS stays on mains instead of cycling the battery every hour.

Three-level inverter, 94.5–95.5%

Lower switching loss and a cleaner waveform, which also means less heat inside a small tower cabinet.

Internal or external battery

K models ship with internal 12 V blocks for install-and-run; KL models use the same chassis with a larger external bank where runtime matters.

Starts without a battery

Useful on site: the UPS can be commissioned and the load transferred before the battery bank is connected.

Generator compatible, 40–70 Hz

Frequency converter mode (50 in / 60 out or the reverse) for equipment sourced from another market.

Technical specifications

GT Series 1–3 kVA

Six models, 208/220/230/240 Vac, output power factor 1.0.

ParameterGT1KGT1KLGT2KGT2KLGT3KGT3KL
Capacity
Capacity (VA / W)1 kVA / 1000 W1 kVA / 1000 W2 kVA / 2000 W2 kVA / 2000 W3 kVA / 3000 W3 kVA / 3000 W
TechnologyDouble conversion online
PhaseSingle phase in / single phase out
Input
WiringL / N + PE
Rated voltage208 / 220 / 230 / 240 Vac
Voltage range90–285 Vac
Frequency range40–70 Hz
Input power factor≥0.99
Output
WiringL / N + PE
Output voltage208 / 220 / 230 / 240 Vac
Output power factor1.0
Voltage regulation±1%
Output frequency50/60 Hz ±4 Hz sync mode; 50/60 Hz ±0.1% free run
WaveformPure sine wave
Distortion<2% linear load; <5% non-linear load
Crest factor3:1
OverloadWarning above 100%; bypass after 30 min at 102–110%; 10 min at 110–130%; 30 s at 130–150%; 200 ms above 150%
Efficiency
AC / AC mode94.5%94.5%95.5%95.5%95.5%95.5%
DC / AC mode89.5%89.5%91.5%91.5%91.5%91.5%
Battery
Rated battery voltage24 Vdc36 Vdc48 Vdc72 Vdc72 Vdc96 Vdc
Battery locationInternalExternalInternalExternalInternalExternal
Battery capacity12 V / 7 Ah × 2 pcsDepends on external bank12 V / 7 Ah × 4 pcsDepends on external bank12 V / 7 Ah × 6 pcsDepends on external bank
Backup time at half load>6 minDepends on external bank>6 minDepends on external bank>6 minDepends on external bank
Charging current1 A5.5 A1 A5.5 A1 A5.5 A
Interface
DisplayLCD — input voltage, frequency, load level, operating mode, health status
Standard portRS232
Optional cardsSNMP (app / web / PC monitoring, server and NAS shutdown), MODBUS, USB, RS485, AS400 relay card
Environment & physical
Operating temperature−10 to 50 °C
Relative humidity0–98% non-condensing
Audible noise<55 dB at 1 m
ChassisTower
Dimensions L × W × H280×144×230 mm400×144×230 mm400×144×230 mm400×144×230 mm425×190×328 mm400×144×230 mm
Weight8.9 kg4.5 kg14 kg5.6 kg19 kg6.4 kg

Specifications subject to change without notice. Output is 208/220/230/240 Vac on this page. The 1–3 kVA models are also built in a 110/115/120/127 V version, listed separately as GT Series 1–3 kVA (110/120 V) — the output is set at the factory, so confirm the site voltage when ordering. For split-phase 120/240 V output with an isolation transformer, see the GT Series 6–20 kVA DP.

Technical specifications

GT Series 6–10 kVA

Four models, 208/220/230/240 Vac, output power factor 1.0.

ParameterGT6KGT6KLGT10KGT10KL
Capacity
Capacity (VA / W)6 kVA / 6000 W6 kVA / 6000 W10 kVA / 10,000 W10 kVA / 10,000 W
TechnologyDouble conversion online, three-level inverter
PhaseSingle phase in / single phase out
Input
WiringL / N + PE
Rated voltage208 / 220 / 230 / 240 Vac
Voltage range120–275 Vac
Frequency range40–70 Hz
Input power factor≥0.99
Output
WiringL / N + PE
Output voltage208 / 220 / 230 / 240 Vac
Output power factor1.0
Voltage regulation±1%
Output frequency50/60 Hz ±4 Hz sync mode; 50/60 Hz ±0.1% free run
WaveformPure sine wave
Distortion<2% linear load; <5% non-linear load
Crest factor3:1
Overload1 min at 105–125%; 30 s at 125–135%; 300 ms above 135%
Efficiency
AC / AC mode>93%
DC / AC mode>91%
Battery
Rated battery voltage192 Vdc192 / 240 Vdc192 Vdc192 / 240 Vdc
Battery locationInternalExternalInternalExternal
Battery capacity12 V / 7 Ah × 16 pcsDepends on external bank12 V / 7 Ah × 16 pcsDepends on external bank
Backup time at half load>6 minDepends on external bank>6 minDepends on external bank
Charging current1 A5.5 A1 A5.5 A
Interface
DisplayLCD — input voltage, frequency, load level, operating mode, health status
Standard portRS232
Optional cardsSNMP (app / web / PC monitoring, server and NAS shutdown), MODBUS, relay card
Environment & physical
Operating temperature−10 to 50 °C
Relative humidity0–98% non-condensing
Audible noise<55 dB at 1 m
ChassisTower
Dimensions L × W × H533×260×560 mm425×190×328 mm533×260×560 mm533×260×501 mm
Weight55 kg12.2 kg62 kg21 kg

Specifications subject to change without notice. Output is 208/220/230/240 Vac on this page. The 1–3 kVA models are also built in a 110/115/120/127 V version, listed separately as GT Series 1–3 kVA (110/120 V) — the output is set at the factory, so confirm the site voltage when ordering. For split-phase 120/240 V output with an isolation transformer, see the GT Series 6–20 kVA DP.

Warranty

12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.

Sizing a 1–10 kVA tower UPS?

Tell us the load in kW, the runtime required and the site voltage. We will confirm the model and whether internal battery is enough.

Request a quote

Related products

Other platforms

RT Series · 1–10 kVA

RT Series · 1–10 kVA

The same range, rack or tower, output PF 1.0.

View series →
GT Series · 6–20 kVA DP

GT Series · 6–20 kVA DP

Split phase 120/240 V with isolation.

View series →
SR Series · 1–20 kVA

SR Series · 1–20 kVA

Rack-mounted double-conversion UPS.

View series →