Online UPS · 208/220/230/240 Vac · PF 1.0
GT Series 1–10 kVA
The tower workhorse of the range: true double conversion from 1 to 10 kVA at 208/220/230/240 V, with output power factor 1.0 — a 10 kVA unit carries 10 kW, not 9.
Ten models: GT1K / GT2K / GT3K with internal battery, GT1KL / GT2KL / GT3KL for external banks, and GT6K / GT6KL / GT10K / GT10KL above 6 kVA.
Design highlights
Why output power factor 1.0 matters here
Most UPS in this class are rated at 0.9 PF, so a 10 kVA unit carries 9 kW. At 1.0 the same frame carries 10 kW — often the difference between one model and the next size up, which is a real cost difference on a project.
Wide enough to ride out the brownouts and generator dips that a 208/220 V site actually sees. The UPS stays on mains instead of cycling the battery every hour.
Lower switching loss and a cleaner waveform, which also means less heat inside a small tower cabinet.
K models ship with internal 12 V blocks for install-and-run; KL models use the same chassis with a larger external bank where runtime matters.
Useful on site: the UPS can be commissioned and the load transferred before the battery bank is connected.
Frequency converter mode (50 in / 60 out or the reverse) for equipment sourced from another market.
Technical specifications
GT Series 1–3 kVA
Six models, 208/220/230/240 Vac, output power factor 1.0.
| Parameter | GT1K | GT1KL | GT2K | GT2KL | GT3K | GT3KL |
|---|---|---|---|---|---|---|
| Capacity | ||||||
| Capacity (VA / W) | 1 kVA / 1000 W | 1 kVA / 1000 W | 2 kVA / 2000 W | 2 kVA / 2000 W | 3 kVA / 3000 W | 3 kVA / 3000 W |
| Technology | Double conversion online | |||||
| Phase | Single phase in / single phase out | |||||
| Input | ||||||
| Wiring | L / N + PE | |||||
| Rated voltage | 208 / 220 / 230 / 240 Vac | |||||
| Voltage range | 90–285 Vac | |||||
| Frequency range | 40–70 Hz | |||||
| Input power factor | ≥0.99 | |||||
| Output | ||||||
| Wiring | L / N + PE | |||||
| Output voltage | 208 / 220 / 230 / 240 Vac | |||||
| Output power factor | 1.0 | |||||
| Voltage regulation | ±1% | |||||
| Output frequency | 50/60 Hz ±4 Hz sync mode; 50/60 Hz ±0.1% free run | |||||
| Waveform | Pure sine wave | |||||
| Distortion | <2% linear load; <5% non-linear load | |||||
| Crest factor | 3:1 | |||||
| Overload | Warning above 100%; bypass after 30 min at 102–110%; 10 min at 110–130%; 30 s at 130–150%; 200 ms above 150% | |||||
| Efficiency | ||||||
| AC / AC mode | 94.5% | 94.5% | 95.5% | 95.5% | 95.5% | 95.5% |
| DC / AC mode | 89.5% | 89.5% | 91.5% | 91.5% | 91.5% | 91.5% |
| Battery | ||||||
| Rated battery voltage | 24 Vdc | 36 Vdc | 48 Vdc | 72 Vdc | 72 Vdc | 96 Vdc |
| Battery location | Internal | External | Internal | External | Internal | External |
| Battery capacity | 12 V / 7 Ah × 2 pcs | Depends on external bank | 12 V / 7 Ah × 4 pcs | Depends on external bank | 12 V / 7 Ah × 6 pcs | Depends on external bank |
| Backup time at half load | >6 min | Depends on external bank | >6 min | Depends on external bank | >6 min | Depends on external bank |
| Charging current | 1 A | 5.5 A | 1 A | 5.5 A | 1 A | 5.5 A |
| Interface | ||||||
| Display | LCD — input voltage, frequency, load level, operating mode, health status | |||||
| Standard port | RS232 | |||||
| Optional cards | SNMP (app / web / PC monitoring, server and NAS shutdown), MODBUS, USB, RS485, AS400 relay card | |||||
| Environment & physical | ||||||
| Operating temperature | −10 to 50 °C | |||||
| Relative humidity | 0–98% non-condensing | |||||
| Audible noise | <55 dB at 1 m | |||||
| Chassis | Tower | |||||
| Dimensions L × W × H | 280×144×230 mm | 400×144×230 mm | 400×144×230 mm | 400×144×230 mm | 425×190×328 mm | 400×144×230 mm |
| Weight | 8.9 kg | 4.5 kg | 14 kg | 5.6 kg | 19 kg | 6.4 kg |
Specifications subject to change without notice. Output is 208/220/230/240 Vac on this page. The 1–3 kVA models are also built in a 110/115/120/127 V version, listed separately as GT Series 1–3 kVA (110/120 V) — the output is set at the factory, so confirm the site voltage when ordering. For split-phase 120/240 V output with an isolation transformer, see the GT Series 6–20 kVA DP.
Technical specifications
GT Series 6–10 kVA
Four models, 208/220/230/240 Vac, output power factor 1.0.
| Parameter | GT6K | GT6KL | GT10K | GT10KL |
|---|---|---|---|---|
| Capacity | ||||
| Capacity (VA / W) | 6 kVA / 6000 W | 6 kVA / 6000 W | 10 kVA / 10,000 W | 10 kVA / 10,000 W |
| Technology | Double conversion online, three-level inverter | |||
| Phase | Single phase in / single phase out | |||
| Input | ||||
| Wiring | L / N + PE | |||
| Rated voltage | 208 / 220 / 230 / 240 Vac | |||
| Voltage range | 120–275 Vac | |||
| Frequency range | 40–70 Hz | |||
| Input power factor | ≥0.99 | |||
| Output | ||||
| Wiring | L / N + PE | |||
| Output voltage | 208 / 220 / 230 / 240 Vac | |||
| Output power factor | 1.0 | |||
| Voltage regulation | ±1% | |||
| Output frequency | 50/60 Hz ±4 Hz sync mode; 50/60 Hz ±0.1% free run | |||
| Waveform | Pure sine wave | |||
| Distortion | <2% linear load; <5% non-linear load | |||
| Crest factor | 3:1 | |||
| Overload | 1 min at 105–125%; 30 s at 125–135%; 300 ms above 135% | |||
| Efficiency | ||||
| AC / AC mode | >93% | |||
| DC / AC mode | >91% | |||
| Battery | ||||
| Rated battery voltage | 192 Vdc | 192 / 240 Vdc | 192 Vdc | 192 / 240 Vdc |
| Battery location | Internal | External | Internal | External |
| Battery capacity | 12 V / 7 Ah × 16 pcs | Depends on external bank | 12 V / 7 Ah × 16 pcs | Depends on external bank |
| Backup time at half load | >6 min | Depends on external bank | >6 min | Depends on external bank |
| Charging current | 1 A | 5.5 A | 1 A | 5.5 A |
| Interface | ||||
| Display | LCD — input voltage, frequency, load level, operating mode, health status | |||
| Standard port | RS232 | |||
| Optional cards | SNMP (app / web / PC monitoring, server and NAS shutdown), MODBUS, relay card | |||
| Environment & physical | ||||
| Operating temperature | −10 to 50 °C | |||
| Relative humidity | 0–98% non-condensing | |||
| Audible noise | <55 dB at 1 m | |||
| Chassis | Tower | |||
| Dimensions L × W × H | 533×260×560 mm | 425×190×328 mm | 533×260×560 mm | 533×260×501 mm |
| Weight | 55 kg | 12.2 kg | 62 kg | 21 kg |
Specifications subject to change without notice. Output is 208/220/230/240 Vac on this page. The 1–3 kVA models are also built in a 110/115/120/127 V version, listed separately as GT Series 1–3 kVA (110/120 V) — the output is set at the factory, so confirm the site voltage when ordering. For split-phase 120/240 V output with an isolation transformer, see the GT Series 6–20 kVA DP.
12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.
Sizing a 1–10 kVA tower UPS?
Tell us the load in kW, the runtime required and the site voltage. We will confirm the model and whether internal battery is enough.