Online UPS · 110 / 115 / 120 / 127 V
GT Series 1–3 kVA, 110/120 V
The same GT platform, built for 110 V grids: Latin America, parts of the Middle East, marine and remote telecom sites. A 60–138 Vac input window means it copes with supplies that swing far below the nameplate.
Six models: GT1K / GT2K / GT3K with internal battery, GT1KL / GT2KL / GT3KL for external banks.
Design highlights
Why the 110 V version is not just a different plug
Wide even by 110 V standards. On a weak feeder the UPS stays on mains instead of cycling the battery every hour — which is what actually kills battery life.
110, 115, 120 or 127 Vac selectable. The 127 V setting matters in Brazil and Mexico, where equipment is often imported set to 120 V and runs hot.
Higher than the 240 V GT, because the lower voltage means lower switching losses in this topology. At 3 kVA that is roughly 150 W less heat inside the cabinet.
Internal 12 V / 7 Ah banks on the K models; KL models take an external bank sized to the site.
50 Hz in, 60 Hz out or the reverse — for equipment sourced from a different market, without adding a separate converter.
Cold start, wide input tolerance and adjustable charging, so a small genset does not trip the UPS on load step.
Technical specifications
GT Series 1–3 kVA, 110/120 V
Six models, tower chassis.
| Parameter | GT1K | GT1KL | GT2K | GT2KL | GT3K | GT3KL |
|---|---|---|---|---|---|---|
| Capacity | ||||||
| Capacity (VA / W) | 1 kVA / 900 W | 1 kVA / 900 W | 2 kVA / 1.8 kW | 2 kVA / 1.8 kW | 3 kVA / 2.7 kW | 3 kVA / 2.7 kW |
| Technology | Double conversion online | |||||
| Phase | 1 phase in / 1 phase out | |||||
| Input | ||||||
| Wiring | L / N + PE | |||||
| Rated voltage | 110 / 115 / 120 / 127 Vac | |||||
| Voltage range | 60–138 Vac | |||||
| Frequency range | 40–70 Hz | |||||
| Input power factor | ≥0.99 | |||||
| Output | ||||||
| Wiring | L / N + PE | |||||
| Output voltage | 110 / 115 / 120 / 127 Vac | |||||
| Output power factor | 0.9 (1.0 optional) | |||||
| Voltage regulation | ±1% | |||||
| Output frequency | 50/60 Hz ±4 Hz sync mode; 50/60 Hz ±0.1% free run | |||||
| Waveform | Pure sine wave | |||||
| Distortion | <2% linear load; <5% non-linear load | |||||
| Crest factor | 3:1 | |||||
| Overload | Warning above 100%; bypass after 30 min at 102–110%; 10 min at 110–130%; 30 s at 130–150%; 200 ms above 150% | |||||
| Efficiency | ||||||
| AC / AC mode | 94.5% | 94.5% | 95.5% | 95.5% | 95.5% | 95.5% |
| DC / AC mode | 89.5% | 89.5% | 91.5% | 91.5% | 91.5% | 91.5% |
| Battery | ||||||
| Rated battery voltage | 24 Vdc | 36 Vdc | 48 Vdc | 72 Vdc | 72 Vdc | 96 Vdc |
| Battery location | Internal | External | Internal | External | Internal | External |
| Battery capacity | 12 V / 7 Ah × 2 pcs | Depends on external bank | 12 V / 7 Ah × 4 pcs | Depends on external bank | 12 V / 7 Ah × 6 pcs | Depends on external bank |
| Backup time at full load | 7–10 min | Depends on external bank | 7–10 min | Depends on external bank | 7–10 min | Depends on external bank |
| Charging current | 1 A | 5.5 A | 1 A | 5.5 A | 1 A | 5.5 A |
| Interface | ||||||
| Display | LCD — input voltage, frequency, load level, operating mode, health status | |||||
| Standard port | RS232 | |||||
| Optional cards | SNMP (app / web / PC monitoring, server and NAS shutdown), MODBUS, relay card assembled per order | |||||
| Environment & physical | ||||||
| Operating temperature | −10 to 50 °C | |||||
| Relative humidity | 0–98% non-condensing | |||||
| Audible noise | <55 dB at 1 m | |||||
| Chassis | Tower | |||||
| Dimensions L × W × H | 350×144×230 mm | 350×144×230 mm | 425×190×328 mm | 425×190×328 mm | 425×190×328 mm | 425×190×328 mm |
| Weight | 11.5 kg | 6 kg | 22.2 kg | 10 kg | 27.5 kg | 11 kg |
Specifications subject to change without notice. KL models are supplied without internal batteries; runtime depends on the external bank configured for the site. A 220/230/240 V version of the same platform is available — ask for the GT 1–3 kVA 240 V datasheet.
12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.
Selling into a 110/127 V market?
Tell us the country and the plug standard. We ship the output voltage preset and can supply cord sets to match the market.
Related products
Other platforms



GT Series · 6–10 kVA
Single-phase double-conversion tower UPS with internal or external battery.