TD Series Low-Frequency UPS 3–40 kVA

Online UPS · With output isolation transformer

TD Series 3–40 kVA

A low-frequency online UPS built around a full-bridge topology and an output isolation transformer. Slower to build than a high-frequency unit, and the reason it survives surges and short circuits that destroy them.

3–40 kVACapacity
0.8Output PF
0 msTransfer
TransformerGalvanic isolation

TD11: single-phase in, single-phase out, 3–20 kVA. TD31: three-phase in, single-phase out, 10–40 kVA.

Design highlights

Why low frequency still wins on hard loads

Output isolation transformer

Full-bridge topology with a transformer on the output: stronger inrush capability and a real barrier against load-side faults.

Handles the loads high-frequency units refuse

Motors, compressors, medical imaging and welding equipment draw currents that a transformerless UPS simply cannot ride through.

Intelligent charging, 1–25 A

Charge current is set on the LCD panel to match battery type, capacity and duty cycle, which is what actually extends battery life.

Dual AC input

Main and bypass inputs can come from two different sources, so one failed feeder does not take the UPS down.

Frequency and phase adaptive

Output tracks 50 or 60 Hz from the mains and locks to the input phase sequence automatically.

DSP control, 93–94% efficiency

Full digital control with ECO mode taking efficiency above 97% when the load tolerates it.

Technical specifications

TD11 Series — single phase in / single phase out

3 to 20 kVA, 220 Vac single-phase supply.

ParameterTD11 3 kVATD11 6 kVATD11 10 kVATD11 15 kVATD11 20 kVA
Capacity
Rated power3 kVA / 2.4 kW6 kVA / 4.8 kW10 kVA / 8 kW15 kVA / 12 kW20 kVA / 16 kW
TechnologyTrue online double conversion, microcontroller controlled
Input
Voltage220 Vac ±25%
Input form1P2W + G
Frequency40–70 Hz
Output
Voltage220 Vac ±1%
Output form1P2W + G
Frequency50/60 Hz ±1%, auto sensing
Efficiency AC/AC>92%
Transfer time0 ms
WaveformSine wave
Power factor0.8
Voltage T.H.D.≤3% linear, ≤8% non-linear
Crest factor3:1
Output overload105% ±5%: overload warning; >105% to 125%: bypass after 2 min; >125% to 150%: bypass after 30 s; >150%: bypass after 500 ms
Battery
Battery typeVRLA (valve regulated lead acid)
DC voltage192 Vdc
Charging time4 hours to 90%
Battery detectionSelf-detect, transfer to battery mode adjustable
Environment
Altitude1700 m above sea level without derating
Temperature & noise0 to 40 °C / <60 dB at 1.5 m
Humidity0–95% non-condensing
Physical
Dimensions (mm)533 × 260 × 501560 × 260 × 717560 × 260 × 717655 × 370 × 900655 × 370 × 900
Net weight40 kg65 kg79.5 kg122 kg152 kg

Specifications subject to change without notice. TD31 output is single phase; for three-phase output above 60 kVA see the ST33 series.

Technical specifications

TD31 Series — three phase in / single phase out

10 to 40 kVA, 380 Vac three-phase supply, single-phase output.

ParameterTD31 10 kVATD31 15 kVATD31 20 kVATD31 30 kVATD31 40 kVA
Capacity
Rated power10 kVA / 8 kW15 kVA / 12 kW20 kVA / 16 kW30 kVA / 24 kW40 kVA / 32 kW
TechnologyTrue online double conversion, microcontroller controlled
Input
Voltage380 Vac ±25%
Input form3P4W + G
Frequency40–70 Hz
Output
Voltage220 Vac ±1%
Output form1P2W + G
Frequency50/60 Hz ±1%, auto sensing
Efficiency AC/AC>92%
Transfer time0 ms
WaveformSine wave
Power factor0.8
Voltage T.H.D.≤3% linear, ≤8% non-linear
Crest factor3:1
Output overload105% ±5%: overload warning; >105% to 125%: bypass after 2 min; >125% to 150%: bypass after 30 s; >150%: bypass after 500 ms
Battery
Battery typeVRLA (valve regulated lead acid)
DC voltage192 Vdc192 Vdc192 Vdc384 Vdc384 Vdc
Charging time4 hours to 90%
Environment
Altitude1700 m above sea level without derating
Temperature & noise0 to 40 °C / <60 dB at 1.5 m
Humidity0–95% non-condensing
Physical
Dimensions (mm)560 × 267 × 717655 × 370 × 900830 × 455 × 1055830 × 455 × 1055830 × 515 × 1355
Net weight79.5 kg122 kg195 kg210 kg285 kg

Specifications subject to change without notice. TD31 output is single phase; for three-phase output above 60 kVA see the ST33 series.

Warranty

12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.

Not sure whether you need low frequency?

Send the load type — motors, imaging equipment, IT, mixed. We will tell you honestly whether a transformer-based unit is worth the weight and cost.

Request a quote

Related products

Other platforms

ST33 Series · 60–160 kVA

ST33 Series · 60–160 kVA

Three-phase power-module UPS for data centers and IT rooms.

View series →
RM Series · 30–600 kVA

RM Series · 30–600 kVA

Modular N+X redundant UPS with hot-swappable 30/50 kVA modules.

View series →
GT Series · 6–10 kVA

GT Series · 6–10 kVA

Single-phase double-conversion tower UPS with internal or external battery.

View series →