Online UPS · With output isolation transformer
TD Series 3–40 kVA
A low-frequency online UPS built around a full-bridge topology and an output isolation transformer. Slower to build than a high-frequency unit, and the reason it survives surges and short circuits that destroy them.
TD11: single-phase in, single-phase out, 3–20 kVA. TD31: three-phase in, single-phase out, 10–40 kVA.
Design highlights
Why low frequency still wins on hard loads
Full-bridge topology with a transformer on the output: stronger inrush capability and a real barrier against load-side faults.
Motors, compressors, medical imaging and welding equipment draw currents that a transformerless UPS simply cannot ride through.
Charge current is set on the LCD panel to match battery type, capacity and duty cycle, which is what actually extends battery life.
Main and bypass inputs can come from two different sources, so one failed feeder does not take the UPS down.
Output tracks 50 or 60 Hz from the mains and locks to the input phase sequence automatically.
Full digital control with ECO mode taking efficiency above 97% when the load tolerates it.
Technical specifications
TD11 Series — single phase in / single phase out
3 to 20 kVA, 220 Vac single-phase supply.
| Parameter | TD11 3 kVA | TD11 6 kVA | TD11 10 kVA | TD11 15 kVA | TD11 20 kVA |
|---|---|---|---|---|---|
| Capacity | |||||
| Rated power | 3 kVA / 2.4 kW | 6 kVA / 4.8 kW | 10 kVA / 8 kW | 15 kVA / 12 kW | 20 kVA / 16 kW |
| Technology | True online double conversion, microcontroller controlled | ||||
| Input | |||||
| Voltage | 220 Vac ±25% | ||||
| Input form | 1P2W + G | ||||
| Frequency | 40–70 Hz | ||||
| Output | |||||
| Voltage | 220 Vac ±1% | ||||
| Output form | 1P2W + G | ||||
| Frequency | 50/60 Hz ±1%, auto sensing | ||||
| Efficiency AC/AC | >92% | ||||
| Transfer time | 0 ms | ||||
| Waveform | Sine wave | ||||
| Power factor | 0.8 | ||||
| Voltage T.H.D. | ≤3% linear, ≤8% non-linear | ||||
| Crest factor | 3:1 | ||||
| Output overload | 105% ±5%: overload warning; >105% to 125%: bypass after 2 min; >125% to 150%: bypass after 30 s; >150%: bypass after 500 ms | ||||
| Battery | |||||
| Battery type | VRLA (valve regulated lead acid) | ||||
| DC voltage | 192 Vdc | ||||
| Charging time | 4 hours to 90% | ||||
| Battery detection | Self-detect, transfer to battery mode adjustable | ||||
| Environment | |||||
| Altitude | 1700 m above sea level without derating | ||||
| Temperature & noise | 0 to 40 °C / <60 dB at 1.5 m | ||||
| Humidity | 0–95% non-condensing | ||||
| Physical | |||||
| Dimensions (mm) | 533 × 260 × 501 | 560 × 260 × 717 | 560 × 260 × 717 | 655 × 370 × 900 | 655 × 370 × 900 |
| Net weight | 40 kg | 65 kg | 79.5 kg | 122 kg | 152 kg |
Specifications subject to change without notice. TD31 output is single phase; for three-phase output above 60 kVA see the ST33 series.
Technical specifications
TD31 Series — three phase in / single phase out
10 to 40 kVA, 380 Vac three-phase supply, single-phase output.
| Parameter | TD31 10 kVA | TD31 15 kVA | TD31 20 kVA | TD31 30 kVA | TD31 40 kVA |
|---|---|---|---|---|---|
| Capacity | |||||
| Rated power | 10 kVA / 8 kW | 15 kVA / 12 kW | 20 kVA / 16 kW | 30 kVA / 24 kW | 40 kVA / 32 kW |
| Technology | True online double conversion, microcontroller controlled | ||||
| Input | |||||
| Voltage | 380 Vac ±25% | ||||
| Input form | 3P4W + G | ||||
| Frequency | 40–70 Hz | ||||
| Output | |||||
| Voltage | 220 Vac ±1% | ||||
| Output form | 1P2W + G | ||||
| Frequency | 50/60 Hz ±1%, auto sensing | ||||
| Efficiency AC/AC | >92% | ||||
| Transfer time | 0 ms | ||||
| Waveform | Sine wave | ||||
| Power factor | 0.8 | ||||
| Voltage T.H.D. | ≤3% linear, ≤8% non-linear | ||||
| Crest factor | 3:1 | ||||
| Output overload | 105% ±5%: overload warning; >105% to 125%: bypass after 2 min; >125% to 150%: bypass after 30 s; >150%: bypass after 500 ms | ||||
| Battery | |||||
| Battery type | VRLA (valve regulated lead acid) | ||||
| DC voltage | 192 Vdc | 192 Vdc | 192 Vdc | 384 Vdc | 384 Vdc |
| Charging time | 4 hours to 90% | ||||
| Environment | |||||
| Altitude | 1700 m above sea level without derating | ||||
| Temperature & noise | 0 to 40 °C / <60 dB at 1.5 m | ||||
| Humidity | 0–95% non-condensing | ||||
| Physical | |||||
| Dimensions (mm) | 560 × 267 × 717 | 655 × 370 × 900 | 830 × 455 × 1055 | 830 × 455 × 1055 | 830 × 515 × 1355 |
| Net weight | 79.5 kg | 122 kg | 195 kg | 210 kg | 285 kg |
Specifications subject to change without notice. TD31 output is single phase; for three-phase output above 60 kVA see the ST33 series.
12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.
Not sure whether you need low frequency?
Send the load type — motors, imaging equipment, IT, mixed. We will tell you honestly whether a transformer-based unit is worth the weight and cost.
Related products
Other platforms


RM Series · 30–600 kVA
Modular N+X redundant UPS with hot-swappable 30/50 kVA modules.
View series →
GT Series · 6–10 kVA
Single-phase double-conversion tower UPS with internal or external battery.
View series →