SHINPOWIN™ Power Protection Request a quote
ST33 Series Three-Phase UPS 60–160 kVA

Online UPS · Three phase in / three phase out

ST33 Series 60–160 kVA

Power-module three-phase UPS for small and medium data centers, IT rooms and dispatch centres. Three-level conversion, 0 ms transfer, and a frame that parallels to four units when the room grows.

60–160 kVACapacity
≥94.5%Efficiency
1.0Output PF (100 kVA+)
±192 VdcBattery (default)

Five models, 60 to 160 kVA. Battery banks of 32–40 blocks; paralleled units can share one bank.

Design highlights

Built to be maintained, not replaced

Power module design

Rectifier and inverter are replaceable modules, so service does not mean taking the whole load down for a day.

Three-level topology

Lower switching losses and a cleaner output waveform — this is where the ≥94.5% efficiency figure comes from.

0 ms transfer

True double conversion: the load never sees a break, on mains or on battery.

Parallel to four units

Units share load and battery bank, so capacity can grow with the room instead of being bought up front.

Wide input tolerance

208–478 Vac operating range and 173–500 Vac bypass, for grids that are not what the nameplate claims.

Battery flexibility

32–40 blocks at ±192 Vdc default, with adjustable charge current from 20 A to 54 A depending on model.

Technical specifications

ST33 Series 60–160 kVA

Five models, three-phase input and three-phase output.

ParameterST33 60KSST33 80KSST33 100KSST33 120KSST33 160KS
Capacity
Rated power60 kVA / 54 kW80 kVA / 72 kW100 kVA / 100 kW120 kVA / 120 kW160 kVA / 160 kW
Input
Phase3 phase 4 wires + ground
Rated voltage380 / 400 / 415 Vac
Operating voltage range208–478 Vac
Operating frequency45–55 Hz at 50 Hz / 54–66 Hz at 60 Hz, self-adapting
Power factor>0.99
Harmonic distortion (THDi)≤3% at 100% non-linear load
Bypass voltage range173–500 Vac (380/400/415 Vac)
Bypass frequency protection±10%
Generator inputSupported
Output
Phase3 phase 4 wires + ground
Output voltage380 / 400 / 415 Vac ±1%
Rated current91 A121 A151 A181 A243 A
Output power factor0.90.91.01.01.0
Voltage regulation±1%
Output frequencyUtility: 50 Hz (46–54 Hz) / 60 Hz (56–64 Hz); battery: (50/60 ±0.1%) Hz
Crest factor3:1
Harmonic wave≤2% linear, ≤5% non-linear
Efficiency≥94.5% in normal mode
Overload≤110% for 60 min; ≤125% for 10 min; ≤150% for 1 min; >150% shutdown immediately
Battery
Rated voltage±192 Vdc (default)
Number of blocks32–40 pcs (optional)
Charge current20 A max20 A max24 A adjustable36 A adjustable54 A adjustable
Transfer time
Utility to battery0 ms
Utility to bypass0 ms
Environment
Operating temperature0 to 40 °C
Storage temperature−25 to 55 °C, no battery
Humidity0–95% non-condensing
Altitude<1500 m
Noise level<60 dB
Protection & communication
AlarmOverload, utility abnormal, UPS fault, battery low
ProtectionShort circuit, overload, over temperature, battery low, fan fault
CommunicationRS232 / USB / relay card / SNMP (optional); parallel function (optional)
StandardsEN62040-1, EN62040-2
Physical
Dimensions D × W × H865 × 302 × 970 mm865 × 302 × 970 mm1000 × 430 × 1200 mm1000 × 430 × 1200 mm1000 × 600 × 1200 mm
Net weight87 kg87 kg169 kg169 kg249 kg

Specifications subject to change without notice. Battery configuration and runtime are sized per project — request the current datasheet for tender use.

Warranty

12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.

Sizing a three-phase UPS for a project?

Send the load list, required runtime and the site's supply voltage. We come back with a model, a battery configuration and a price.

Request a quote

Related products

Other platforms

GT Series · 6–10 kVA

GT Series · 6–10 kVA

Single-phase double-conversion tower UPS with internal or external battery.

View series →
RM Series · 30–600 kVA

RM Series · 30–600 kVA

Modular N+X redundant UPS with hot-swappable 30/50 kVA modules.

View series →
TD Series · 3–40 kVA

TD Series · 3–40 kVA

Low-frequency UPS with output isolation transformer.

View series →