Hybrid inverter · 230 Vac · Built-in WiFi
VM IV 4–6 kW
A fourth-generation hybrid inverter for homes and small commercial sites. The practical difference from the earlier VM series is the built-in WiFi, the 4.3-inch colour display and the ability to run with no battery connected at all.
Two models: VM IV 4000W (24 V battery) and VM IV 6000W (48 V battery).
Design highlights
Built for installers, not catalogues
Battery-independent design means the inverter can be commissioned and used as a straight PV inverter, with storage added later.
Firmware updates, parameter rewrites and data downloads from a USB stick — no laptop and no dongle on site.
Events are stored inside the inverter, so a fault that cleared itself is still visible when you arrive.
Input range, charging source priority, charging current and output usage window are all set from the panel, per installation.
Technical specifications
VM IV 4–6 kW
Two models, 230 Vac single phase.
| Parameter | VM IV 4000W | VM IV 6000W |
|---|---|---|
| Input | ||
| Rated power | 4000 VA / 4000 W | 6000 VA / 6000 W |
| Nominal voltage | 230 Vac | |
| Low loss voltage | 170 ±7 Vac (UPS mode); 90 ±7 Vac (appliance mode) | |
| Low loss return voltage | 180 ±7 Vac (UPS); 100 ±7 Vac (appliance) | |
| High loss voltage | 280 ±7 Vac | |
| High loss return voltage | 270 ±7 Vac | |
| Maximum AC input voltage | 300 Vac | |
| Nominal input frequency | 60/50 Hz, auto sensing | |
| Low loss frequency | 40 ±1 Hz; return at 42 ±1 Hz | |
| High loss frequency | 65 ±1 Hz; return at 63 ±1 Hz | |
| Output short-circuit protection | Circuit breaker | |
| Inverter output | ||
| Efficiency in line mode | >95% at rated resistive load, battery fully charged | |
| Transfer time | 10 ms typical (UPS mode); 20 ms typical (appliance mode) | |
| Output voltage regulation | 230 Vac ±5% | |
| Output frequency | 50/60 Hz ±1% | |
| Peak efficiency | 94% | |
| Overload protection | 5 s at ≥110% load; 10 s at 105–110% | |
| Surge capacity | 2 × rated power for 5 s | |
| Battery | ||
| Nominal DC input voltage | 24 Vdc | 48 Vdc |
| Cold start voltage | 23 Vdc | 46 Vdc |
| Low DC cut-off | 21 Vdc | 42 Vdc |
| High DC cut-off | 33 Vdc | 63 Vdc |
| No-load consumption | <40 W | <55 W |
| Charging | ||
| Charging algorithm | 3-step | |
| Maximum charging current | 100 A | |
| Bulk charging voltage | 29.2 V flooded / 28.2 V AGM-GEL | 58.4 V flooded / 56.4 V AGM-GEL |
| Floating charge voltage | 27 Vdc | 54 Vdc |
| MPPT solar charger | ||
| Maximum PV array power | 5000 W | 6000 W |
| Maximum PV current | 27 A | |
| Nominal PV voltage | 320 Vdc | 360 Vdc |
| MPPT operating range | 60–450 Vdc | |
| Maximum PV open circuit voltage | 500 Vdc | |
| Maximum charging current | 120 A | |
| General | ||
| Communication port | RS232 / USB / BMS (RS485, CAN-BUS or RS232) | |
| Operating humidity | 5–95% relative, non-condensing | |
| Operating temperature | 0 to 55 °C | |
| Storage temperature | −15 to 60 °C | |
| Net weight | 10 kg | 12 kg |
Specifications subject to change without notice. Loss and return voltages are configurable from the LCD panel. Battery type profiles cover flooded, AGM and GEL lead acid.
12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.