GT Series · 6–10 kVA
Single-phase double-conversion tower UPS with internal or external battery.
View series →
Line-interactive UPS · 500–3000 VA
An entry-level line-interactive UPS with AVR, for workstations, POS terminals, routers and small office equipment. Eight models from 500 VA to 3000 VA (the 1000 VA unit is marked D-1000 on the chassis), in 110/120 V and 220/230/240 V versions.
Battery-mode output is a simulated sine wave. For loads with active PFC power supplies, specify an online unit instead.
Design highlights
Boost and buck taps hold the output in range without switching to battery, which is why this class lasts longer on dirty grids than its price suggests.
85–150 Vac on 110 V models, 145–290 Vac on 220 V models — it keeps working through brownouts that would flatten a basic offline unit.
No continuously running inverter. For workstations and network gear, the efficiency and cost difference is real.
Two front-panel options: LED indicators for cost-sensitive orders, LCD for installations where staff need to read load and battery state.
Starts on battery with no mains present — useful during commissioning and for equipment moved between sites.
Simulated sine wave in battery mode and 2–8 ms transfer. Fine for adapters and small IT loads; not for motors or medical equipment.
Technical specifications
Eight models, 110/120 V and 220/230/240 V versions.
| Parameter | SO-500 | SO-600 | SO-800 | SO-1000 | SO-1200 | SO-1500 | SO-2000 | SO-3000 |
|---|---|---|---|---|---|---|---|---|
| Capacity | ||||||||
| Capacity | 300 W | 360 W | 480 W | 600 W | 720 W | 900 W | 1200 W | 1800 W |
| Input | ||||||||
| Voltage | 110/120 Vac or 220/230/240 Vac | |||||||
| Voltage range | 85–150 Vac / 145–290 Vac | |||||||
| Frequency range | 45–65 Hz | |||||||
| Output | ||||||||
| AC voltage regulation, battery mode | 110/120 Vac or 220/230/240 Vac ±10% | |||||||
| Frequency, battery mode | 50 Hz ±1 Hz or 60 Hz ±1 Hz | |||||||
| Transfer time | Typical 2–8 ms, 10 ms maximum | |||||||
| Waveform, battery mode | Simulated sine wave | |||||||
| Battery | ||||||||
| Battery voltage | 12 V | 12 V | 12 V | 24 V | 24 V | 24 V | 24 V | 24 V |
| Battery configuration | 4.5 Ah × 1 | 7 Ah × 1 | 9 Ah × 1 | 7 Ah × 2 | 7 Ah × 2 | 9 Ah × 2 | 9 Ah × 2 | 9 Ah × 2 × 2 |
| Charging period | 4–6 hours to 90% | |||||||
| Maximum charge current | 1.0 A | 1.0 A | 1.0 A | 1.0 A | 1.0 A | 1.0 A | 1.0 A | 2.0 A |
| Indication & protection | ||||||||
| Indicators | AC mode: green. Battery mode: orange flash. Fault: red | |||||||
| Protection | Short circuit, overload, overcharge and overdischarge | |||||||
| Alarm | Battery mode every 10 s; low battery every 1 s; overload every 0.5 s; fault continuous | |||||||
| Physical | ||||||||
| Dimensions D × W × H | 255×98×140 mm | 300×95×140 mm | 300×95×140 mm | 330×122×192 mm | 330×122×192 mm | 345×122×192 mm | 345×122×192 mm | 412×145×210 mm |
| Net weight | 4 kg | 4.7 kg | 5.5 kg | 7.8 kg | 9.6 kg | 11.2 kg | 14.7 kg | 19 kg |
| Environment | ||||||||
| Humidity | 0–90% RH at 0–40 °C, non-condensing | |||||||
| Noise level | <40 dB | |||||||
| Communication port | RS232 / USB optional | |||||||
Model marking: the SO-1000 unit carries D-1000 on the front panel; order codes above are the SO series codes. Specifications subject to change without notice. Output in battery mode is a simulated sine wave with a typical 2–8 ms transfer — this class of UPS is not suitable for active-PFC server supplies, motors or medical equipment. For those loads see the GT or TD series.
12 months on the UPS unit against manufacturing defects. Wear parts and battery banks are covered by their own terms — ask for the current statement before quoting.
Tell us the target market, the plug type and the panel preference (LED or LCD). We quote by container and support private label.
Related products

Single-phase double-conversion tower UPS with internal or external battery.
View series →