Online UPS · 1–3 kVA
Tower and rackmount, pure sine wave, for servers and network closets.
View series →
Online UPS · Single phase
True double-conversion tower UPS for servers, network rooms and small industrial loads. A wide 120–275 Vac input window keeps it on inverter only when it has to be — not every time the grid dips.
Four models: GT6K, GT6KL, GT10K, GT10KL. KL models run on an external battery bank for long backup times.
Design highlights
AC is rectified and rebuilt continuously, so the load never sees a transfer to battery. Output stays a pure sine wave with ±1% voltage regulation.
Most of the export markets we serve sit far outside a nominal ±10%. A wide window means fewer unnecessary battery cycles and longer battery life.
Active PFC keeps reflected harmonics low, which matters when the UPS shares a generator or a weak transformer.
GT6K and GT10K ship with 12 V / 7 Ah × 16 internal batteries for ~6 minutes at half load. GT6KL and GT10KL take an external bank sized to the project.
RS232 is standard. SNMP, MODBUS and relay cards are available for remote monitoring, server and NAS shutdown, and BMS integration.
OEM and private-label options, spare parts and technical support for partners maintaining installed bases in their own market.
Technical specifications
Full parameter table for the GT6K, GT6KL, GT10K and GT10KL models.
| Parameter | GT6K | GT6KL | GT10K | GT10KL |
|---|---|---|---|---|
| General | ||||
| Capacity (VA / W) | 6 kVA / 5.4 kW | 6 kVA / 5.4 kW | 10 kVA / 9 kW | 10 kVA / 9 kW |
| Topology | Double conversion online | Double conversion online | Double conversion online | Double conversion online |
| Phase | 1 in / 1 out | 1 in / 1 out | 1 in / 1 out | 1 in / 1 out |
| Input | ||||
| Wiring | L / N + PE | L / N + PE | L / N + PE | L / N + PE |
| Rated voltage | 208 / 220 / 230 / 240 Vac | 208 / 220 / 230 / 240 Vac | 208 / 220 / 230 / 240 Vac | 208 / 220 / 230 / 240 Vac |
| Voltage range | 120–275 Vac | 120–275 Vac | 120–275 Vac | 120–275 Vac |
| Frequency range | 40–70 Hz | 40–70 Hz | 40–70 Hz | 40–70 Hz |
| Input power factor | ≥ 0.99 | ≥ 0.99 | ≥ 0.99 | ≥ 0.99 |
| Output | ||||
| Wiring | L / N + PE | L / N + PE | L / N + PE | L / N + PE |
| Rated voltage | 208 / 220 / 230 / 240 Vac | 208 / 220 / 230 / 240 Vac | 208 / 220 / 230 / 240 Vac | 208 / 220 / 230 / 240 Vac |
| Output power factor | 0.9 (1.0 optional) | 0.9 (1.0 optional) | 0.9 (1.0 optional) | 0.9 (1.0 optional) |
| Voltage regulation | ±1% | ±1% | ±1% | ±1% |
| Frequency | 50/60 Hz ±4 Hz sync · ±0.1% free run | 50/60 Hz ±4 Hz sync · ±0.1% free run | 50/60 Hz ±4 Hz sync · ±0.1% free run | 50/60 Hz ±4 Hz sync · ±0.1% free run |
| Waveform | Pure sine wave | Pure sine wave | Pure sine wave | Pure sine wave |
| Harmonic distortion | <2% linear · <5% non-linear | <2% linear · <5% non-linear | <2% linear · <5% non-linear | <2% linear · <5% non-linear |
| Crest factor | 3:1 | 3:1 | 3:1 | 3:1 |
| Overload capability | 105–125%: transfer to bypass after 1 min with alarm · 125–135%: after 30 s · >135%: after 300 ms | |||
| Efficiency | ||||
| AC / AC mode | >93% | >93% | >93% | >93% |
| DC / AC mode | >91% | >91% | >91% | >91% |
| Battery & charging | ||||
| Rated battery voltage | 192 Vdc | 192 / 240 Vdc | 192 Vdc | 192 / 240 Vdc |
| Battery configuration | Internal | External | Internal | External |
| Battery capacity | 12 V / 7 Ah × 16 pcs | Depends on external bank | 12 V / 7 Ah × 16 pcs | Depends on external bank |
| Backup time at half load | >6 min | Depends on external bank | >6 min | Depends on external bank |
| Charging current | 1 A | 5.5 A | 1 A | 5.5 A |
| Physical | ||||
| Chassis | Tower | Tower | Tower | Tower |
| Dimensions L × W × H (mm) | 533 × 260 × 560 | 425 × 190 × 328 | 533 × 260 × 560 | 533 × 260 × 501 |
| Weight | 55 kg | 12.2 kg | 62 kg | 21 kg |
| Interface & communication | ||||
| Display | LCD — input voltage, frequency, load level, operating mode, health status | |||
| Standard port | RS232 | |||
| Optional cards | SNMP card (remote monitoring via smartphone app, web page or PC software; server and NAS shutdown) · MODBUS card · relay card, assembled per order before shipment | |||
| Environment | ||||
| Operating temperature | -10 to 50 °C | -10 to 50 °C | -10 to 50 °C | -10 to 50 °C |
| Relative humidity | 0–98% non-condensing | 0–98% non-condensing | 0–98% non-condensing | 0–98% non-condensing |
| Audible noise | <55 dB at 1 m | <55 dB at 1 m | <55 dB at 1 m | <55 dB at 1 m |
KL models are supplied without internal batteries; backup time is configured per project. Specifications are subject to change without notice — request the current datasheet for tender use.
Send the load, required runtime and destination market. We reply with a model selection, battery configuration and price.
Related products

Tower and rackmount, pure sine wave, for servers and network closets.
View series →
1–3 kVA for 110/120 V grids in Latin America, the Middle East and marine sites.
View series →
MPPT, parallel capable, open BMS protocol for solar and storage sites.
View series →