The constraint
Floor area. The room was built around the racks, and the UPS had to fit into what was left: a corridor-width strip against the wall, with front access only.
The site also wanted the battery outside the UPS cabinet. Internal batteries would have meant replacing the whole unit when the bank reached end of life, and limited runtime to what fits in the chassis.
What was installed
A 30 kVA ST33 three-phase high-frequency UPS with front access, feeding a rack-mounted external bank sized to the runtime the site asked for.
Three-phase input keeps the load balanced across the phases — on a single-phase unit at this capacity the neutral current alone becomes a design problem. The external bank means runtime can be extended later without replacing the UPS.
What it means for a similar site
Between roughly 10 and 40 kVA the choice is usually between a bigger single-phase tower and a small three-phase frame. If the incoming supply is three-phase and the load is balanced, the three-phase unit runs cooler and draws a lower neutral current. If the room has no depth, front access matters more than efficiency on the datasheet.